Briefing

Forced Entry and Ballistic Resistance Are Separate Specifications

Interior of a hardened secure room with exposed concrete walls and a steel door

A protective wall is often specified against one question: will it stop a bullet? A second question is just as important for many facilities, and it is answered by a different test. How long will the wall, the door or the louver hold out against a person with tools who is trying to get through it? The first is a ballistic question. The second is a forced-entry question. A product that answers one has not, by that fact alone, answered the other.

This note is written for architects, engineers, specifiers, facility owners and contracting officers who write or review requirements for secure rooms, guard positions, equipment enclosures and building perimeters. It explains how forced-entry tests work, what they measure, and how to write both requirements into a specification so that neither is assumed.

What a ballistic test does not measure

UL 752, the Standard for Bullet-Resisting Equipment, and NIJ Standard-0108.01, Ballistic Resistant Protective Materials, fire defined rounds at a specimen and record whether they penetrate. They are ballistic tests. Neither sends a team with sledgehammers, pry bars or cutting tools against the specimen, and neither times how long the specimen delays a person trying to make an opening.

That matters because a forced-entry attack goes after different things. A rifle round strikes the face of a panel. A person with tools works on hinges, frame anchors, glazing stops, louver blades, joints between panels and the edge where a door meets the wall. A wall section can perform well against a round and still have a frame or a joint that gives way quickly to a pry bar. The specification has to ask both questions, and it has to ask them of the assembly, not only of the wall.

Forced-entry tests measure time

Forced-entry test methods share a basic idea. A test team attacks a specimen with a defined set of tools, and the result is the time the specimen resists before the team creates an opening large enough to pass a defined test object.

ASTM F3038, the Standard Test Method for Timed Evaluation of Forced-Entry-Resistant Systems, is one common reference. ASTM describes it as a method to evaluate the time necessary for personnel to create an opening of sufficient size, and states that it is designed to simulate a spontaneous mob using readily available hand tools. Its scope lists windows, doors, modular panels, glazings, louvers, walls, seismic joints, roofs, roof hatches, grilles and similar products. Under the method, all portions of the tested specimen must meet the test level for the specimen to receive a rating.

The U.S. Department of State standard SD-STD-01.01, Forced Entry and Ballistic Resistance of Structural Systems, is another reference used for high-security doors, windows and similar assemblies. It combines a timed forced-entry test with a ballistic test, and its forced-entry levels are expressed in minutes, with 5, 15 and 60 minute levels. A designation under it states the forced-entry time and whether ballistic resistance was also tested.

Other ASTM methods address particular elements. ASTM F2781 is a practice for testing the forced-entry resistance of security fence systems. ASTM F3561 tests the forced-entry resistance of fenestration systems after a simulated active shooter attack, which reflects the way an attacker may fire at glazing and then try to break through it.

What drives the result

ASTM F3038 identifies three factors that determine whether a forced-entry attack succeeds: the tools and devices used, the number of attackers, and the sophistication of the attack. Those three factors are the forced-entry equivalent of the round, velocity and shot pattern in a ballistic test. A time result means little unless it is read together with the team size and tool set it was achieved against.

For the same reason, a forced-entry time is not a property of a material. It belongs to the tested assembly: the panel or wall, the frame, the anchorage, the hardware and the way they were installed. Change the hinge, the anchor or the substrate the frame is fixed into, and the tested result may no longer describe what is being built.

Six things a forced-entry requirement should state

A specification that says only “forced-entry resistant” gives the submitter nothing to test against and the owner nothing to accept against. Each of these should be written down.

  • The attack. The number of attackers and the class of tools assumed, in plain words, drawn from the facility’s risk assessment.
  • The delay required. The time the barrier must hold, set against the time it takes responders to arrive after detection.
  • The test method and edition. The standard the assembly must be tested to, named with its year or revision.
  • The assembly. The wall, door, window, louver or hatch together with its frame, anchorage, hardware and the construction it is fixed into.
  • The ballistic requirement, if any. Written separately, with its own standard and threat, and with a statement of whether both must be met by the same tested assembly.
  • The evidence. The full test report for each assembly, showing the team, tools, time and result, not a summary line on a data sheet.

Time only works with response

Forced-entry resistance buys time. It does not end an attack. The delay a barrier provides is useful only if someone is alerted and can respond before the time runs out. That is why a forced-entry requirement should start with the facility’s detection and response plan, not with a catalog. A barrier that delays an attacker for a set number of minutes protects the room only if detection is early enough and the response is fast enough to arrive inside that window. Where response is slow, the answer may be earlier detection or more layers of delay rather than a single heavier door.

The weakest element sets the time

A secure room is only as resistant as the easiest way into it. A high-delay wall with a lightly anchored door frame, an unprotected louver, a roof hatch or a utility penetration offers the attacker a shorter path. Each opening and penetration in the protective line needs its own requirement against the same attack, and each needs its own test evidence. The same reasoning applies to ballistic protection, and it is set out in more detail in how to read a ballistic test report before you specify.

Where Amidon fits

Amidon designs, supplies and installs protective construction, and it keeps the ballistic and forced-entry questions separate in its submittals. Amidon Shield is used in cast-in-place and precast protective walls and enclosures, and ArmorBlock brings the same material into masonry construction. For openings, Amidon supplies forced-entry and ballistic louvers and confirms the tested basis for the exact configuration before it goes on a submittal. Amidon’s design and engineering group works with the project engineer to write the attack and the threat, select assemblies against both, and assemble the test records that go with them.

Amidon is a Service-Disabled Veteran-Owned Small Business (SDVOSB).

Writing a ballistic wall specification

Writing a forced-entry requirement?

Send the attack and threat your facility has to resist and the openings you need to protect. Amidon will respond with an assembly approach and the test records that apply to it for engineering review.

Talk to Amidon